SCOPE:
Installation of GU Convertible Collar Liner
with flexible compression seal gasket to form a water tight connection
at the precast concrete manhole flat top slab or precast concrete
manhole cones and the grade adjustment (brick masonry, precast concrete
grade rings*, or field poured concrete collar.) Note: In order to
mount the GU Compression seal gasket; the precast concrete manhole
top slab or cone must have access of 1 1/2" greater opening diameter
then the I.D. of the GU Convertible Collar Liner to be installed.
(i.e. 24" I.D. access GU Convertible Collar Liner
requires a 25.5" opening / gasket mount in precast structure )
|
|
INSTALLATION:
(1) Inspection precast concrete. Top slab / cone
for correct access opening diameter and for damage / irregularity
which would prevent proper installation and seal.
(2) Clean dirt and / or excess concrete slurry from gasket mount
area.
(3) Assemble precast manhole in the customary manner as prescribed
by the precast manufacturer and the approved construction plans.
GU Convertible Collar Liner for brick masonry or precast concrete
grade rings* shall be used at grade to complete assembly of fully
lined manhole if adjustment is necessary.
(4) Insert GU Lip Seal Gasket as prescribed. NOTE: The outer
/ upper lip of the gasket shall place evenly around the top interior
edge of access opening. The gasket inner seal fins must be oriented
down toward interior of access opening.
(5) Insert GU Convertible Collar Liner through the installed
GU Lip Seal Gasket / precast access and deflect to conform
accurately to the finished ground or pavement grade / as shown on
the drawings or as directed by the engineer. Precast concrete grade
rings* must be set on manhole flat top slab and/ or precast manhole
cone sections BEFORE GU Convertible Collar Liner is installed.
(6) To provide grade adjustment for accurate setting of cast iron
frames, brick masonry or precast concrete grade rings* or field
poured concrete shall be set on top of manhole flat top slab and/
or precast manhole cone.
*IMPORTANT NOTE - precast concrete grade rings must have interior
access opening diameter 1" to 1.5" greater than the I.D. of the
GU Convertible Collar to be installed (i.e. 24" I.D. access GU Convertible
Collar requires a 25" to 25.5" opening in precast concrete grade
ring).
Set precast grade spacer rings or brick masonry in a full bed of
non-shrink mortar in customary manner so that the space between
each ring or brick course is completely filled. (Be sure to apply
sufficient mortar to the GU Convertible Collar Liner and
brick courses so the vertical space between liner and brick masonry
is completely filled).
(7) Manhole Frame shall be "sealed" to the top flange of the GU
Convertible Collar with approved Butyl Rubber Preformed Flexible
Joint Sealant** . It is recommended that the butyl rubber sealant
strip be approximately 1/4" to 3/8" thick by 3/4" to 1 1/4" wide
(dimensions vary per sealant manufacturer). **Butyl Rubber Preformed
Flexible Joint Sealant "gasket material" shall comply with most
current revision of Standard Specification ASTM C990, Section
6.2 - Butyl Rubber Sealant and Federal Specification SS-S-210A
type I and shall be applied per manufacturer's instructions. (NOTE:
Thicker sealant strips which are typically used for precast concrete
structure joints are too thick and may prevent accurately setting
the GU Brick Adjustment Chimney Liner and the cast iron frame
to the correct grade.) . The cast iron frame and cover shall be
installed as prescribed by utility specifications or as directed
by the engineer.
(8) There shall be no exposed mortar through inside liner collar
surface at cast iron cover frame ring joint or the precast manhole
flat top slabs and precast manhole cones section joint which will
permit the passage of liquid or gases through the liner wall to
masonry adjustment or precast concrete sections
|