(A)
Scope
The wetwell manhole liner shall be a FIBERGLASS REINFORCED PLASTIC (F.R.P.) LINER SYSTEM, which is resistant to the chemical environment normally found in wastewater transmission systems. The F.R.P. Liner shall be a non-load bearing component integrally cast and adequately anchored inside new precast concrete wetwell sections during concrete casting process at the concrete precaster's manufacturing facility. |
(B)
FIBERGLASS WETWELL LINER
(1) The prefabricated F.R.P. liner shall be a one piece construction of unlayered, homogenous composite with minimum thickness shall be 1/8" (3 mm) and shall be in lengths and nominal inside diameters corresponding to the precast concrete wetwell section (2) Watertight gasketed pipe bell connections or F.R.P. / PVC boot hole sleeves to suit specific pipe types, grade and alignment, shall be monolithically attached to prefabricated F.R.P. liner to extend to the outside profile of the precast concrete structure per drawing details (3) Prefabricated F.R.P. liner for wetwell flat top shall extend vertically through hatch opening return and be sealed to hatch frame with an elastomeric sealant approved by the liner manufacturer. (4) The outer surface of the liner to be aggregate coated and have steel spirals/ lattice bonded to the F.R.P. to insure anchoring to concrete sections. |
|
(C)
INSTALLATION IN PRECAST CONCRETE |
(D)
FIELD ASSEMBLY AND INSPECTION PRECAST CONCRETE WETWELL WITH F.R.P. LINER
|
|
PROTECTIVE
LINER
GU FIBERGLASS REINFORCED PLASTIC (F.R.P.) CONCRETE PROTECTIVE LINER |
|
Scope:
Furnish fiberglass reinforced plastic (F.R.P.) of polyurethane hybrid polymer resin to be installed in sanitary sewer manholes and lift station/ wetwells as a protective surface barrier. The F.R.P. polyurethane hybrid polymer liner shall be a non load-bearing component, which is resistant to the chemical environment normally found in wastewater collection systems. The liner shall be prefabricated rigid F.R.P. sections of unlayered homogeneous composite with an aggregate coated outer surface to insure adequate mechanical anchoring of F.R.P. liner to concrete/ grout in sanitary sewer structures. |
2.0 Materials: F.R.P. Polyurethane
Hybrid Polymer Composite
2.1 Minimum Thickness: (A) Integrally cast in new precast concrete structures Minimum thickness 3/16" (5 mm) (B) Field installed rehab/ retrofit into existing sanitary manholes Minimum thickness 1/4" (7 mm) 2.2 Material Properties (A) Fiberglass (Type E Glass) Minimum length of fibers = 0.625 inches Content by weight 12% - 15% (B) Inert Filler Content by weight 10% - 13% (C) Bonding aggregate - prewashed, kiln dried, fractured 3/8" gravel Graded particle size minimum 3/16" and maximum 3/8" Rate of application - 3.5 lb/ sq ft |
||||||||||||||||||||||||||||||||||
| 2.3 Physical Properties
(A) Abrasion resistance - Falling Sand (ASTM D968) Thickness of material removed passes
(B) Density of F.R.P. Polyurethane Hybrid Composite (ASTM D1622) - 1.17g/cm3 (C) Shore "A" Hardness Durometer (ASTM D2240) - Exceeds 90 on scale (D) Percolation Test - Water absorption of top surface - 0.032% (E) Thermal shock (CSA-B45-M93) 100 thermal cycles- no sign of surface defects 2.4 Chemical Resistance (A) Chemical Resistance (Selected Reagents) (ASTM D1308)
(B) Acetone Immersion (ASTM. D2152) - No attack NOTE: For comprehensive Precast or Rehab/ Retrofit liner specifications refer to GU Fiberglass Plastic Liner Specifications for GU F.R.P. Manhole Base Liner, GU F.R.P. Manhole Liner, GU F.R.P. Wetwell Liner and GU F.R.P. Rehab Liner. |
|||||||||||||||||||||||||||||||||||